BP-7478513 N 0 0 X 0 m m IL W Z Q Ln m 0 FOR G()NSTRUCTION Scope of Work: RGS Energy shall install a 4.400 kW Grid -tied Photovoltaic ("PV") System totaling (16) Solarworld Plus SW 275 Mono Black Modules with (16) Enphase Energy M250-60-2LL-S22 Micro- Inverter(s). The Modules shall be flush mounted on the asphalt/comp. shingle roof and interconnected via load side breaker connection. Equipment Specifications: Module: (16) Solarworld Plus SW 275 Mono Black Inverter 1: (16) Enphase Energy M250-60-2LL-S22 Racking: UniRac SolarMount Attachment Flashing: Eco-Fasten Green -Fasten with CP-SQ-Slotted Bracket and Aluminum Flashing Roof Specifications: Roof 1: Asphalt/Comp. Shingle (Single Layer) 2" x 10" Rafters @ 24" O.C. Pitch:40' 1 Azimuth: 160° Array Size: 16 Modules Site Specifications: Occupancy: 11 Design Wind Speed: 110 MPH Exposure Category: C Mean Roof Height: 25 ft Ground Snow Load: 30 PSF (Reducible) Adj. Roof Snow Load: 11.6 PSF All Work to be in Compliance with: 2014 National Electrical Code (NEC) 2009 International Residential Code (IRC) 2009 International Building Code (IBC) 2012 International Fire Code (IFC) 2012 Uniform Mechanical Code (UMC) 2012 Uniform Plumbing Code (UPC) MA 780 CMR, 8th Edition -including 2/4/11 revisions to Tables R301.2(4) & R301.2(5) ASCE/ANSI 7-05 Minimum Design Loads for Buildings and Other Structures As amended and adopted by Town of Dartmouth Grid -Tied Photovoltaic System DC Rating: 4.400 kW Garfield, Natalie 194 Gaffney Rd S. Dartmouth, MA 02748 Jurisdiction: Town of Dartmouth General Notes: 1. System follows any/all Fire Code Setbacks per Ordinances of the Town Of Dartmouth. 2. All projects will comply with the Ordinances of the Town of Dartmouth. 3. Construction Hours: 7am-8pm Monday -Friday, 9am-8pm Saturday, No time on Sunday or legal Holidays. 4. Product Data Sheets shall be included. 5. Rooftop penetrations shall be completed and sealed per code by a licensed contractor. 6. All Photovoltaic modules shall be tested and listed by a recognized laboratory. 7. Certifications shall include UL1703, IEC61646, IEC61730. 8. A continuous ground shall be provided for the Array and for all Photovoltaic Equipment. 9. DC Wiring shall be run in metal conduit or raceways within enclosed spaces in a building. 10. Conduit, Wire systems and Raceways shall be located as close as possible to ridges, hips, and outside walls. 11. Conduit between Sub Arrays and to DC Combiners/Disconnects shall use guidelines that minimize the total amount of conduit by taking the shortest path. 12. Space Requirements for electrical equipment shall comply with NEC Article 110. 13. Equipment grounding shall be sized in accordance with Table 250.122. 14. Connectors that are not readily accessible and that are used in the circuits operating at or over 30V AC or DC shall require a tool for opening and are required to be marked "Do not disconnect under load" or "Not for current interrupting", per 690.33 (c) & (e). 15. All signage to be placed in accordance with local building code. 16. Signs or Directories shall be attached to the electrical equipment or located adjacent to the identified equipment. 17. Signs should be of sufficient durability to withstand the environment. 18. Any plaques shall be metal or plastic with engraved or machine printed letters, or electro-plating, in a red background with white lettering, a minimum of 3/8" height and all capital letters. Sheet List Sheet No. Sheet Title PV-000 COVER PV-A01 SITE PLAN PV-A02 MODULE LAYOUT PV-A03 DETAILS PV-A04 MATERIALS PV-E01 ELECTRICAL DIAGRAM PV-E02 SYSTEM CALCS PV-G01 SIGNAGE 32 Taugwonk Spur, Al2 Stonginton, CT 06378 Phone (860) 535-3370 Fax (413) 683-2225 GRID -TIED PHOTOVOLTAIC SYSTEM 4.400kW DC @ STC GARFIELD, NATALIE 194 GAFFNEY RD S. DARTMOUTH, MA 02748 Project # 10135199 DESIGNER: DKN REVIEWER: CR VERSION DATE. 2014-08-25 REVISIONS # BY Date Notes 1 2 3 4 5 sE N/A *91TU7 PV-000 FAR t^mSTRUGTION N 4 a N S m Ln r (E) Single Family Dwelling �11/ 1 .­ -, . 16 Solarworld Plus SW 275 Mono Black Modules 16 Enphase Energy M250-60-2LL-S22 Micro -Inverters Asphalt/Comp. Shingle Roof 2" X 10" Rafters @ 24" O.C. Pitch:40° Azimuth:160° (E) Accessory Building Equipment Location: Exterior (E) Utilty Meter (N) PV Production Meter/Monitor (N) PV AC Disconnect Equipment Location: Interior (E) Main Service Panel - POI RS 32 Taugwonk Spur, Al2 Stonginton, CT 06378 Phone (860) 53-3370 Fax (413) 683-2225 GRID -TIED PHOTOVOLTAIC SYSTEM 4.400kW DC @ STC GARFIELD, NATALIE 194 GAFFNEY RD S. DARTMOUTH, MA 02748 Project # 10135199 DESIGNER: DKN REVIEWER: CR VERSION DATE. 2014-08-25 REVISIONS 1# I By I Date I Notes I SC4LE. 111= 20' SITE PLAN PV-A01 m N 2 FOB GUr�STRUCTION PV ARRAY 1 - MECHANICAL LOADS Array Area: 296.1 ft2 Total Photovoltaic Dead Load: 3.25 psf Array Weight: 962.8 Ibs Avg. Dead Load per Anchor: 30.1 Ibs Anchor Qty.: 1 32 Design Values by Roof Zone: Corner Egde Interior Max. UniRac Rail Span: 60 in O.C. 60 in. O.C. 60 in.. O.C. Max. UniRac Rail Cantilever: 20 in. O.C. 20 in. O.C. 20 in. O.C. Adjusted Anchor Span: ................................................................................. 48 in.. O.C. 48 in.. O.C. 48 in: O O.C. Downforce Point Load: 343.6 Ibs 343.E Ibs 343.6 Ibs Uplift Point Load: ................................................................................. -295.7 Ibs .295.7 Ibs -240.8 Ibs 707 Ibs Minimum Anchor Strength: 2.70 Average Safety Factor: • Total Quantity of Attachments =32 • Roof Zones are defined by dimension, a = 3.0 ft. • Maximum Allowable Cantilever for UniRac Rail is Y3 the Maximum Rail Span • Racking and Attachment: UniRac SolarMount with Eco-Fasten Green -Fasten with CP-SQ-Slotted Bracket and Aluminum Flashing attached with 5/16" x 3-1/2" Lag Bolt, Hex Head, 18-8 SSs • All Dimensions shown are to module edges, including 1 in. Spacing between Modules required when using the Top Clamp Method. The Rails Extend 3 in. Beyond the module edge. N • UniRac Requires one thermal expansion gap for every run of rail greater than 40' • Array Installed according to the UniRac SolarMount Code -Compliant Installation Manual ver. 227.3, R' Pub 110616-1cc, June 2011 • Attachment Locations, If shown, are approximate. Final adjustment of attachment location may be E necessary depending on field conditions. All attachments are staggered amongst the framing members. S RG c 32 Taugwonk Spur, Al2 Stonginton, CT 06378 Phone (860) 535-3370 Fax (413) 683-2225 GRID -TIED PHOTOVOLTAIC SYSTEM 4.400kW DC @ STC GARFIELD, NATALIE 194 GAFFNEY RD S. DARTMOUTH, MA 02748 Project # 10135199 DESIGNER: DKN REVIEWER: CR VERSION DATE. 2014-08-25 REVISIONS # 113y J Date I Notes — 3/16" = 1'-0" MODULE LAYOUT PV-A02 0 FOR CONI0,TRUCTION T5 M°r° P,us P�spra�'�2­ p G X � Ra�ets 2' ;� Attachment Profile Scale: 3/4" = 1'-0" Ground WEEB & Module Clamp Unirac Solarmount Rail w/ L-foot Green Fasten Flashing: ECO-GF1-BLK-812 With Module (lYf •) ECO-CP-SQ Compression Bracket Rooftop �j/�^ _ 5/16"x 3.5"S.S. Lag Bolt w/2.5" Minimum Pene tration @2Q Sealed w/ Approved Sealant 2"X10 O.Q. Attachment Detail 20" Max 20" Max Roof Framing PV Module Rail Overhang Rail Splice Rail Overhang [—.. I Roof \y Attachment Anchors located -r on alternate roof framing members Sta SS B I' Unir UGC 11 11 l; 11 11 II II II II 11 � 11 II � II 11 11 i it 11 1 �� II 1� I 11 11 � II ,jtil �1 L IFI IIJ ,� 48" Max Anchor Spacin SolarMount Rail Anchor Spacin4 iered Attachment Detail (Typ.) NTS ule Frame rac Rail 5 Groundin Cli &Module Scale: N.T.S. Stagger splice locations within the each row of modules Rail Splice Detail WEEBLug Ground Wire SS Bolt SS Flat Washer Scale: 1" = 1'-0" Min of 2 supports on either side of splice with a max spacing of 60" ,z� vvasner Nut nirac Rail S Bolt 6 Groundin Lu &Rail Scale: N.T.S. NTS a RGS 32 Taugwonk SPur, Al2 Stonginton, CT 06378 Phone (860) 535-3370 Fax (413) 683-2225 GRID -TIED PHOTOVOLTAIC SYSTEM 4.400kW DC @ STC GARFIELD, NATALIE 194 GAFFNEY RD S. DARTMOUTH, MA 02748 Project # 10135199 DESIGNER: DKN REVIEWER: CR VERSION DATE.-2014-08-25j' REVISIONS # I By I Date I Notes s�E VARIES DETAILS PV-A03