BP-86766SCOPE OF WORK
• SYSTEM SIZE: 969OW DC, 816OW AC
• MODULES: (34) REC SOLAR: REC285TP2 BLK
• INVERTER(S):
(1) NINGBO GINLONG TECHNOLOGIES: SOLIS-1P9K-4G-US
• RACKING: SNAPNRACK SERIES 100 UL; FLASHED L FOOT.
SEE PEN D01.
• (1) GINLONG SOLIS RSDAG 1:1 RAPID SHUTDOWN
• (1) GINLONG SOLIS RSD-1G 2:2 RAPID SHUTDOWN
VICINITY MAP
GENERAL NOTES
• ALL WORK SHALL COMPLY WITH 2O17 NEC, 2009 IBC, MUNICIPAL CODE, AND
ALL MANUFACTURERS' LISTINGS AND INSTALLATION INSTRUCTIONS.
• PHOTOVOLTAIC SYSTEM WILL COMPLY WITH 2O17 NEC.
• ELECTRICAL SYSTEM GROUNDING WILL COMPLY WITH 2O17 NEC.
• PHOTOVOLTAIC SYSTEM IS UNGROUNDED. NO CONDUCTORS ARE SOLIDLY
GROUNDED IN THE INVERTER.
• MODULES CONFORM TO AND ARE LISTED UNDER UL 1703.
• INVERTER CONFORMS TO AND IS LISTED UNDER UL 1741.
• RACKING CONFORMS TO AND IS LISTED UNDER UL 2703.
• CONSTRUCTION FOREMAN TO PLACE CONDUIT RUN PER 690.31(G).
• ARRAY DC CONDUCTORS ARE SIZED FOR DERATED CURRENT.
• 9.66 AMPS MODULE SHORT CIRCUIT CURRENT.
• 15.09 AMPS DERATED SHORT CIRCUIT CURRENT [690.8 (a) & 690.8 (b)].
LEGEND AND ABBREVIATIONS
SE SERVICE ENTRANCE
MP MAIN PANEL
SP SUB -PANEL
F01
PV LOAD CENTER
IS-1
SUNRUN METER
PM
DEDICATED PV METER
INVERTER(S) WITH
INV
INTEGRATED DC
DISCONNECT AND AFCI
AC
AC DISCONNECT(S)
DC DC DISCONNECT(S)
[Ed
CB COMBINER BOX
F- -1 INTERIOR EQUIPMENT
LE a SHOWN AS DASHED
TABLE OF CONTENT-S
PAGE # DESCRIPTIr3N
SOLAR MODULES
PV-1.0
COVER SHE -ET
RAIL
PV-2.0
SITE PLP&
PV-3.0
LAYOUT
—
PV-4.0
ELECTRICAL
STANDOFFS &
PV-5.0
SIGNAGI<
FOOTINGS
CHIMNEY
Q
ATTIC VENT
Q
FLUSH ATTIC VENT"
O
PVC PIPE VENT__-Z'
®
METAL PIPE VENT
® T-VENT
SATELLITE DISH
FoFIRE SETBACKS
El HARDSCAPE
— PL— PROPERTY LINE
SCALE: NTS
A
AMPERE
AC
ALTERNATING CURRENT
AFCI
ARC FAULT CIRCUIT INTERRUPTER
AZIM
AZIMUTH
COMP
COMPOSITION
DC
DIRECT CURRENT
(E)
EXISTING
EXT
EXTERIOR
FRM
FRAMING
INT
INTERIOR
LBW
LOAD BEARING WALL
MAG
MAGNETIC
MSP
MAIN SERVICE PANEL
(N)
NEW
NTS
NOT TO SCALE
OC
ON CENTER
PRE-FAB
PRE -FABRICATED
PSF
POUNDS PER SQUARE FOOT
PV
PHOTOVOLTAIC
TL
TYP
TRANSFORMERLESS
TYPICAL
V
VOLTS
W
WATTS
REV
NAME
DATE
COMMENTS
A
#180120
734 FOREST STREET #400, MARLBOROUGH, fMA 01752
PHONE 888,657.6527
FAX 805.528.9701
CUSTOMER RESIDENCE::
ANN SILVA
9 RADCLIFF LN DARTMC)UTH
MA USA 02747
TEL. (508) 992-0167 APN #:0033B:0054tL:0003
PROJECT NUMBER:
221 R-009SILV
DESIGNER: 3031.942.2528
ANDREW HOFFMAN
DRAFTER:
ANDREW HOFFMAN
SHEET
COVER SHEET
REV: A 9/2)8/2017
PAGE PV-1.0
SITE PLAN - SCALE = 1/32" = 1'-0"
® Pt (N) ARRAY AR-01
(N) ARRAY AR-02
Pt
(E) RESIDENCE
r
(N) (1) GINLONG 1:1 RAPID pt
SHUTDOWN DISCONNECT Pc
(N) (1) GINLONG 2:2 RAPID
SHUTDOWN DISCONNECT
INV C j M�
SM AC SE ' '•
o . • , (E) DETACHED
STRUCTURE
-n v
r r
Z
v
r
A�
a�
r
A�
v
r
A�
V
r
A�
ROOF TYPE
AR-01 COMP SHINGLE
AR-02 COMP SHINGLE
D1 - AR-01 - SCALE: 1/8" = V-0"
PITCH: 45'
AZIM: 266'
D2 - AR-02 - SCALE: 3116" = 1'-0"
PITCH: 25'
AZIM: 86'
ATTACHMENT ROOF HEIGHT ROOF FRAME
EXPOSURE MATERIAL
FLASHED L FOOT. SEE PEN D01. TWO STORY ATTIC WOOD
FLASHED L FOOT. SEE PEN D01. TWO STORY ATTIC WOOD
c
1,
1
FRAME TYPE
FRAME
MAX FRAME
OC
ROOF EDGE
MAX RAIL
MAX RAIL
DESIGN CRITERIA
SIZE
SPAN
SPACING
ZONE
SPAN
OVERHANG
MODULES:
RAFTER
2 X 10
10' - 0"
16"
N/A
4'-0"
V-4"
REC SOLAR: REC285TP2 [BLK
RAFTER
2 X 10
16- 2"
16"
N/A
4'-0"
V-4"
MODULE DIMS:
65.94" x 39.25" x 1.49" (38rmm)
MODULE CLAMPS:
Portrait: 8.2" - 16.4"
Landscape: 4.9" - 9.8"
MAX DISTRIBUTED LOALI: 3 PSF
SNOW LOAD: 30 PSF
WIND SPEED:
110 MPH 3-SEC GUST.
LAG SCREWS:
5/16"x3.5": 2.5" MIN EMBEPDMENT
NOTE:
INSTALLERS TO VERIFY [RAFTER
SIZE, SPACING AND SLOPPED
SPANS, AND NOTIFY E.0)'R. OF
ANY DISCREPANCIES BEFORE
PROCEEDING.
PENETRATION SPACING::
FULLY STAGGERED
#180120
734 FOREST STREET #400, MARLBOROUGHJ, MA 01752
PHONE 888.857.8527
FAX 805.528.9701
CUSTOMER RESIDENCE:
ANN SILVA
9 RADCLIFF LN DARTM(OUTH
MA USA 02747
TEL. (508) 992-0167 APN #: 0033B:005UL:0003
PROJECT NUMBER:
221R-009SILV
DESIGNER: 30)3.942.2528
ANDREW HOFFMAN
DRAFTER:
ANDREW HOFFMAN
SHEET
LAYOUT
REV: A 9//28/2017
PAGE PV-3.0
120/240 VAC
SINGLE PHASE
SERVICE
OMETER #:
M EVERSOURCE (MA) 2391964
UTILITY
GRID
SUPPLY SIDE TAP
5
1 EXISTING 200A
(N) LOCKABLE
( MAIN BREAKER
BLADE TYPE
FUSED
J
AC DISCONNECT
iN, EXISTING
200A
MAIN
FACILITY -' '- PANEL
LOADS FACILE-
50A FUSE
_ GROUND
SQUARE D
D222NRB
3R, 60A
120/240VAC
(1) RSD 1:1 RAPID
NINGBO GINLONG
SHUT DOWN DEVICE,
PV MODULES
( N) LOCKABLE
(N) SUN RUN
TECHNOLOGIES:
NEMA 4X, 600v
REC SOLAR: REC285TP2 BLK
BLADE TYPE
CENTRON 4G
SOLIS-IP9K-4G-US
1A /
(12) MODULES
AC DISCONNECT
METER
9000 WATT INVERTER JUNCTION BOX
+(�jff
(1) STRING OF (12) MODULES
OR EQUIVALENT
ic
4
4 4
2
0 -0
M
PV MODULES
IB
ffj
REC SOLAR: REC285TP2 BLK
SQUARE D
DU222RB
240V METER SOCKET
125A CONTINUOUS &
LOAD RATED DC DISCONNECT
WITH AFCI, RAPID SHUTDOWN
r
[-
+
_�
(22) MODULES
(2) STRINGS OF (11) MODULES
3R, 60A,2P
240V METER
COMPLIANT
120/240VAC
200A, FORM 2S
(1) RSD 2:2 RAPID
SHUT DOWN DEVICE,
NEMA 4X, 600V,
WITHIN 1' OF ARRAY
CONDUIT SCHEDULE
#
CONDUIT
CONDUCTOR
NEUTRAL
GROUND
1A
NONE
(2) 10 AWG PV WIRE
NONE
(1) 6 AWG BARE COPPER
1 B
NONE
(4) 10 AWG PV WIRE
NONE
(1) 6 AWG BARE COPPER
2
NONE
(6) 10 AWG PV WIRE
NONE
(1) 6 AWG BARE COPPER
(4) 18 AWG SIGNAL CIRCUIT
WITHIN TC-ER
3
3/4" EMT OR EQUIV.
(6) 10 AWG THHN/THWN-2
NONE
(1) 8 AWG THHN/THWN-2
(2) 14 AWG THHN/THWN-2
SIGNAL CIRCUIT
4
3/4" EMT OR EQUIV.
(2) 6 AWG THHN/THWN-2
(1) 10 AWG THHN/THWN-2
(1) 8 AWG THHN/THWN-2
5
3/4" EMT OR EQUIV.
(2) 6 AWG THHN/THWN-2
(1) 6 AWG THHN/THWN-2
(1) 8 AWG THHN/THWN-2
MODULE CHARACTERISTICS
REC SOLAR: REC285TP2 BLK: 285 W
OPEN CIRCUIT VOLTAGE: 38.6 V
MAX POWER VOLTAGE: 31.9 V
SHORT CIRCUIT CURRENT: 9.66 A
SYSTEM CHARACTERISTICS -INVERTER 1
SYSTEM SIZE:
9690 W
SYSTEM OPEN CIRCUIT VOLTAGE:
522 V
SYSTEM OPERATING VOLTAGE:
383 V
MAX ALLOWABLE DC VOLTAGE:
600 V
SYSTEM OPERATING CURRENT:
26.85 A
SYSTEM SHORT CIRCUIT CURRENT:
36.23 A
NOTES TO INSTALLER:
1. 463 VDC EXPECTED OPEN CIRCUIT STRING VOLTAGE.
2. CONNECT SYSTEM VIA INSULATION PIERCING ON SUPPLY SIDE OF MAIN
BREAKER IN MAIN PANEL ENCLOSURE. CONDUCTORS ARE FIELD INSTALLED.
3. CONNECT THE RAPID SHUTDOWN SIGNAL CIRCUIT CONNECTORS PER
MANUFACTURER SPECIFICATION.
4. SPLICE THE 14 AWG THHN/THWN-2 CONDUCTORS FOR RAPID SHUTDOWN
SIGNAL CIRCUITS INTO 18 AWG CONDUCTORS WITHIN TC-ER CABLE AT THE
JUNCTION BOX.
ELECTRICAL SHOCK HAZARD
DO NOT TOUCH TERMINALS.
TERMINALS ON BOTH THE LINE
AND LOAD SIDES MAY BE
ENERGIZED IN THE OPEN
LABEL LOCATION:
INVERTER(S), AC DISCONNECT(S), AC COMBINER PANEL
(IF APPLICABLE).
PER CODE(S): NEC 2017: 692.17
POWER SOURCE OUTPUT
CONNECTION
DO NOT RELOCATE THIS
OVERCURRENT DEVICE
LABEL LOCATION:
ADJACENT TO PV BREAKER (IF
APPLICABLE).
PER CODE(S): NEC 2017: 705.12(13)(2)(3)(b)
DUAL POWER SUPPLY
SOURCES: UTILITY GRID
AND PV SOLAR ELECTRIC
SYSTEM .
I ARFI I OrATION-
UTILITY SERVICE METER AND MAIN
SERVICE PANEL.
PER CODE(S): CEC 2016: 705.12(D)(3),
NEC 2017: 705.12(B)(3), NEC 2014:
705.12(D)(3), NEC 2011: 705.12(D)(4)
THIS EQUIPMENT FED BY
MULTIPLE SOURCES. TOTAL
RATING OF ALL
OVERCURRENT DEVICES
EXCLUDING MAIN SUPPLY
OVERCURRENT DEVICE SHALL
NOT EXCEED AMPACITY OF
BUSBAR.
LABEL LOCATION:
UTILITY SERVICE METER AND MAIN SERVICE PANEL.
PER CODE(S): CEC 2016: 705.12(D)(2)(3)(c), NEC 2017:
705.12(D)(2)(3)(c), NEC 2014: 705.12(D)(2)(3)(c), NEC
2011: 705.12(D)(4)
IWYAO
® OU :r
LABEL LOCATION:
INTERIOR AND EXTERIOR DC CONDUIT EVERY 10 FT, AT EACH TURN, ABOVE AND
BELOW PENETRATIONS, ON EVERY JB/PULL BOX CONTAINING DC CIRCUITS.
PER CODE(S): CEC 2016: 690.31(G)(3), 690.31(G)(4), NEC 2017: 690.31(G)(3),
690.31(G)(4), NEC 2014: 690.31(G)(3), 690.31(G)(4), NEC 2011: 690.31(E)(3),
690.31(E)(4), IFC 2012: 605.11.1.4
' 10JDD�` 9111*1' U�� s j
wjo n
LABEL LOCATION:
ON OR NO MORE THAN 1 M (3 FT) FROM THE SWITCH.
PER CODE(S): NEC 2017: 690.56(C)(3)
TURN RAPID SHUTDOWN
SWITCH TO THE "OFF"
POSITION TO SHUTDOWN
• w
CONDUCTORS OUTSIDE
_
THE ARRAY.
CONDUCTORS WITHIN
ARRAY REMAIN
ENERGIZED IN SUNLIGHT.
LABEL LOCATION:
ON OR NO MORE THAT 1 M (3 FT) FROM THE SERVICE
DISCONNECTING MEANS TO WHICH THE PV SYSTEMS
ARE CONNECTED.
PER CODE(S): NEC 2017: 690.56(C)(1)(b)
I;ja101 •I'M940Qftt_101116 lif]N Nttillr
LABEL LOCATION:
AC DISCONNECT(S), PHOTOVOLTAIC SYSTEM POINT OF
INTERCONNECTION.
PER CODE(S): CEC 2016: 690.54, NEC 2017: 690.54, NEC
2014: 690.54, NEC 2011: 690.54
PHOTOVOLTAIC SYSTEM
COMBINER PANEL
DO NOT ADD LOADS
LABEL LOCATION:
PHOTOVOLTAIC AC COMBINER (IF
APPLICABLE).
PER CODE(S): CEC 2016:
705.12(D)(2)(3)(c), NEC 2014:
705.12(D)(2)(3)(c), NEC 2011: 705.12(D)(4)
NOTES AND SPECIFICATIONS:
• SIGNS AND LABELS SHALL MEET THE REQUIREMENTS OF THE CEC 2016 AND
NEC 2014 ARTICLE 110.21(B), UNLESS SPECIFIC INSTRUCTIONS ARE REQUIRED
BY SECTION 690, OR IF REQUESTED BY THE LOCAL AHJ.
• SIGNS AND LABELS SHALL ADEQUATELY WARN OF HAZARDS USING EFFECTIVE
WORDS, COLORS AND SYMBOLS.
• LABELS SHALL BE PERMANENTLY AFFIXED TO THE EQUIPMENT OR WIRING
METHOD AND SHALL NOT BE HAND WRITTEN, UNLESS PORTIONS OF LABELS OR
MARKINGS ARE VARIABLE, OR THAT COULD BE SUBJECT TO CHANGES, SHALL
BE PERMITTED TO BE HAND WRITTEN AND SHALL BE LEGIBLE.
• LABEL SHALL BE OF SUFFICIENT DURABILITY TO WITHSTAND THE ENVIRONMENT
INVOLVED.
• SIGNS AND LABELS SHALL COMPLY WITH ANSI Z535.4-2011, PRODUCT SAFETY
SIGNS AND LABELS, UNLESS OTHERWISE SPECIFIED.
• DO NOT COVER EXISTING MANUFACTURER LABELS.
INVERTER 1
$ J : t•] [•YNl •� IG1 lhl • • • •
"4�1%!1rw�► r II "1J ► ' • ' �� •l• ►1 z6.ss
+rr>G: • i� 1 1 1. ,..i • • i dci /. 383
I•�y r r i• i 522
1ll�►�1)1 1 •'a �' * r .•'J` s.7>As" 36.23
LABEL LOCATION:
INVERTER(S), DC DISCONNECT(S).
PER CODE(S): CEC 2016: 690.53, NEC 2014: 690.53, NEC
2011: 690.53
-j:�' 1117 i7ill
Iff
i.
#180120
734 FOREST STREET #400, MARL` -BOROUGH, MA 01752
PHONE 888.657.6527
FAX 805.528.9701
CUSTOMER RESILIENCE:
ANN SILVA
9 RADCLIFF LN DlgRTMOUTH
MA USA 02747
TEL. (508) 992-0167 APN #: 0F033B:0054L:0003
PROJECT NUMBER:
221 R-009SILV
DESIGNER: 303.942.2528
ANDREW HOFFMIAN
DRAFTER:
ANDREW HOFFMIAN
SHEET
SIGNAGE
REV: A 9/28/2017
PAGE PV-5'..p