)TOVOLTAI C SYSTEM NOTES
R PV SYSTEM CAPACITY : 3.57 KW
I11TY AND TYPE OF PV MODULES — (14) LG 255S1C
,RRAY CONFIGURATION: (1) ARRAY OF: (2) STRING
(7) MODULES PER SIRING
IODULE OPEN CIRCUIT VOLTAGE
I ODULE MAX POWER VOLTAGE
MODULE SHORT CIRCUIT CURRENT
AODUL.E MAX POWER CURRENT
IMUM SYSTEM VOLTAGE:
VOLTS (Operating Voltage):
ARRAY TILT: 34 DEGREES
(Voc) = 37.2V
(Vmp) = 30.OV
(Isc) = 8.85A
(Imp) = 8.5A
37.2Vdc X (7) MODULES IN SERIES X (1.13 TEMP FACTOR) = 294.3Vdc
37.2Vdc X (7) MODULES = 260.4Vdc
ARRAY ORIENTATION: 223 DEGREES
i14DE NAME PLATE READING "CO —GENERATION DISCONNECT
RAY CONDUIT 8c WIRING
�E-2; FREE -AIR/ Y27 CONDUIT SLEEVE** FOR WIRING BETWEEN ARRAY MODULES (2) #10 AWG.
DE CONDUIT SLEEVE FOR WIRING BETWEEN ARRAY PANELS AS PER NEC 300.13 & 300.18.
TE VISIT NOTES/PICTURES INDICATED A VACUUM SYSTEM ON THE WALL WHERE THE INVERTERS ARE
D BE MOUNTED THAT WOULD BE REMOVED BY CUSTOMER PRIOR TO INSTALLATION OF PV SYSTEM.
_) UTILITY METER
TILITY DISCONNECT
SOl:rSJLAR, LLC.
20 S"TOW ROAD
MARL #'ON, NJ 08053
PHONE% 609-268-8880
5 clean vi it
PHOTOVOLTAIC f�YSTEM DESIGN DRAWINGS
SCHEVIULE OF REVISIONS
6120112 ORIGINAL DRAWING
DATE DESCRIPTION OF CHANGES
DRAWN BY: 104.1313 CHECKED BY: JG
NJ CERT COF AUTH. 264141920
DRAWING "TITLE:
SFTE PLANS
D RAWI N (s "SHEET:
!� OSE
Cit AN f LO .--►
s C R1 AL.
.496
�IGANT
v_
19
6.
4" STAINLESS
5
16
CP—Sc
GF-1 FLASHING
ROOF JOIST/TRUSS
UNIRAC SOLARMOUNT
. 5 v
L
1
I
MOUNTING NOTES
1. RAFTERS ARE 2X10 @ 16" OC ± 19' 6" SPAN
COLLAR TIES ARE 2X8 @ 16" OC
2. PV MODULES SHALL BE MOUNTED ON ALUMINUM RACKING
3. LAG SCREWS SHALL BE 6" "
X 3
4. RAIL MUST EXTEND 3" BEYOND MODULES
6. THERE MUST BEAT LEAST 12" BETWEEN THE END OF THE RAIL AND THE
OUTSIDE EDGE OF THE END CLAMP
7. L—FOOT SHALL BE LOCATED <26" FROM END OF RAIL, BLOCKING MAY BE
NECESSARY
8. L—FOOT SHALL BE LOCATED WITHIN 1' FROM ANY SPLICE
Q. L—FEET SHALL BE INSTALLED <48" APART
10. WEIGHT OF PV MODULES AND RACKING SHALL BE LESS THAN 5 PSF
4
L
L
FOR LG 255SC1 PANELS:
"L" MUST BE BETWEEN
r1m
5ZIT$G8�ll
and 1
UNIRAC SOLAR MOUNT
311
4
UNIRAC MID CLAMP EXAMPLE
MODU
MODULE
UNIRAC END CLAMP EXAMPLE
I N . 311 ow
MODULE
I UNIRAC
I T r 11, IV
?xl 0
16" O.C.
i"SPAN
SQfILULAR, LLC.
2Cr' STOW ROAD
MARS=,TON, NJ 08053
PHONI 609-268-8880
PHOTOVOLTAI t ; SYSTEM DESIGN DRAWINGS
SCH1i=DULE OF REVISIONS
6/20112
ORIGINAL DRAWING
DATE
DESCRIPTION OF CHANGES
DRAWN BY::' MBB
CHECKED BY: JG
NJ CERT-'OF AUTH. 264141920
DRAWING 771TLE:
MOUNTING
[DETAILS
DRAWING f AHEET:
ft
L
GRID TIED INVERTER #1
MANUFACTURER: FRONIUS
MODEL: IG 4000
MAX SYSTEM VOLTAGE: 500V
RATED INVERTER CAPACITY (WAC): 4000
RATED ARRAY CAPACITY (\N): 3570
RATED INVERTER INPUT CAPACITY (WDC): 5000
RATED AC VOLTAGE: 120/240
OPERATING CURRENT: 16.7A
DC SHORT CIRCUIT CURRENT: 27.6A
DC OPERATING VOLTAGE: 260.4V
UL 1741 LISTED
IEEE 1547 LISTED
GENERAL NOTES
1. BOND PV SYSTEM AND PV RAIL ASSEMBLY TO SERVICE
2. CONNECT AC TO CUSTOMER SERVICE VIA AC COMBINEF
3. ELECTRICAL INSTALLATION SHALL COMPLY WITH NEC 2(
4. INVERTER SHALL COMPLY WITH UL 1741 AND IEEE 154;
5. PROVIDE NAME PLATE ON DC DISCONNECT IN ACCORD/
6. ALL WIRING SHALL BE COOPER UNLESS OTHERWISE NO'
CONDUCTOR DESIGNATION BY CON[
CONDITION
ALLOWABLE CONDUCTOR TYPE(S)
USE-2/R H W-2
FREE AIR
(SUNLIGHT RESISTANT)
RACEWAY
THWN-2 OR XHHW-2 OR RHH/RWH-2
ROOFTOP
RACEWAY OR
THHN OR THWN OR XHHW*
CABLE INDOORS
RACEWAY
UNDERGROUND
THHN OR THWN OR XHHW*
*MAY SUBSTITUTE "-2" RATED CONDUCTORS
kO.".1 n of -unf_% .4 fin
(E) MAIN PANEL (CUTLER -HAMMER)
120/240 VOLT SINGLE PHASE
MAIN CIRCUIT BREAKER RATING: 200A
RUN
,RT
ER
3#1071#6G71"C
] LITY
'CONNECT
DCKABLE)
:MA 3R
3#1011#6G,1"C
TO 2 5A/2 P
ur,vr�uuv �viviPATIBLE
BREAKER AT THE FURTHEST
POSITION OPPOSITE THE
INCOMING UTILITY FEED.
SQl-.ULAR, LLC.
20 SI'TOW ROAD
MARl.r�'O N, NJ 08053
PHONE % 609-268-8880
PHOTOVOLTAIC ;YSTEM DESIGN DRAWINGS
SCHEDIIJLE OF REVISIONS
7/6/12
ADDED GEC
REVISED FUSE SIZE
6/20/12
ORIGINAL DRAWING
DATE
DESCRIPTION OF CHANGES
DRAWN BY: r-MR313
CHECKED BY: JG
NJ CERT O)IF AUTH. 264141920
DRAWING TM iTLE:
ELz',CTRICAL
SIN(GLE LINE
DRAWING WS03IIEET:
.
1. ROOF ACCESS — 24' LADDER
2. ATTIC ACCESS —CLOSET CEILING HATCH (BRING 6' LADDER)
CUSTOMER TO MOVE VACUUM SYSTEM PICTURED BELOW PRIOR
TO INSTALLATION
►-
r
F
..:
: « � yam•„_
o
a � Y
},
2 _
7,
t
a
P �
SOLULAIR, LLC.
20 STOiW ROAD
MARLTO N I , NJ 08053
PHONE: 6019-268_8880
PHOTOVOLTAIC SYSTI�M DESIGN DRAWINGS
SCHEDULE O}~ REVISIONS
6/18112
OR11GINAL DRAWING
DATE
DESCFfiIPTION OF CHANGES
DRAWN BY: MBB
CHECKED BY: JG
NJ CERT OF AUITH. 264141920
DRAWING TITLE:
PICTURE'S/NOTES
DRAWING SHEET; :
INVERTER
PHOTOVOLTAIC DISCONNECT
OPERATING CURRENT:
SHORT CIRCUIT CURRENT:
OPERATING VOLTAGE:
MAXIMUM SYSTEM VOLTAGE:
DC OPERATING VOLTAGES AND MAXIMUM PERMISSIBLE
SYSTEM VOLTAGE ACCORDING TO INVERTER RATING
LOCATION: INVERTERS
DC DISCONNECT
FOR
PHOTOVOLTAIC SYSTEM
AC COMBINER PANEL
FOR
PHOTOVOLTAIC SYSTEM
MOTE: MO OTHER
CIRCUITS TO BE INSTALLED
IN THIS PANEL
LOCATION: AC COMBINER
AC DISCONNECT
PHOTOVOLTAIC SYSTEM
ELECTRIC SHOCK HAZARD!
DC VOLTAGE IS ALWAYS PRESENT WHEN
PV MODULES ARE EXPOSED TO SUNLIGHT
LOCATION: INVERTERS
PHOTOVOLTAIC UTILITY
DISCONNECT
ELECTRIC SHOCK HAZARD!
DO NOT TOUCH TERMINALS.
TERMINALS ON BOTH THE LINE AND LOAD SIDES MAY BE
ENERGIZED IN THE OFF OR OPEN POSITION
LOCATION: ALL EQUIPMENT
INVERTER
MULTIPLE ELECTRICAL POWER SOURCES
PROVIDE POWER TO THIS BUILDING
ELECTRICAL POWER IS PROVIDED BY THE
FOLLOWING SOURCES:
1) UTILITY SERVICE
2) PHOTOVOLTAIC SYSTEM
LOCATION: DC DSICONNECT LOCATION: AC DISCONNECT LOCATION: UTILITY LOCATION: UTILITY EQUIPMENT
DSICONNECT AND MAIN PANEL
CAUTION SOLAR CIRCUIT
LOCATION: EVERY 10'ON
CONDUIT RUNS
p-
SOLlJis AR, LLC,
20 SF=OW ROAD
MARLTOIN, NJ 08053
PHONE: 66509-268-8880
PHOTOVOLTAIC SYf! ITEM DESIGN DRAWINGS